On a brand new cooling tower, we are seeing harmonics of 8 x fan speed despite there being 7 blades.
Driven by a 4 pole AC induction motor with 60 hz current into a torque tube with 2 metal disc couplings into an Amarillo right angle beveled gearbox with a vertical shaft at 209-211 rpm. The sun was too bright to strobe anything. New blades (7), hub, fiberglass shroud and complete fiberglas structure.
Very high amplitude vibration was perceived and motor current higher than predicted so the blade pitch was adjusted from the design of 16 deg all the way down to 12. Motor current dropped as did perceived vibration, but they still were not satisfied, so they called us to check it out.
I took measurements at a common stationary point and found the tip clearance was fairly consistent from 1/2" to 3/4" but the vertical track to be off by almost 3" from the high blade to the low. I couldn't enter the fan to check the shroud concentricity because they only had a little bit of the floor installed. There is a parabolic dish in the center that deflects the airflow and it had significant axial wobble.
So I was all prepared for a little motor speed vibration, maybe some at 209 for so rom the fan and probably axial vibration at vpf in my specturm.
What I got instead was almost nothing at motor speed (good alignment guys), a little sway in the frame at fan speed and a big set of harmonics of 1686 cpm. I can't look at the data, but as I recall it was just about exactly 8 times. There was a smaller vibration at 1055 cpm too.
There was a bit of the siding from the adjacent, dilapidated cooling tower that this one is supposed to replace that was flapping hard against the new one, but I have a hard time believing that it was 1686 cpm. Maybe that was the 1055. They are supposed to fix that. The other issue I identified was in the piping. There was a break in the pipe and it had been taped up with fiberglass tape and supported by comealongs with straps. There was no water flow and the pipe will be repaired and fully supported. I would estimate that it is 20'-24" diameter. I don't know anything about the history behind a brand new, broken 20-24" dia. pipe.
But I'm baffled at the 1686. It was there on the gearbox too, but it didn't take the shape of a bearing vibration at least not wear. I'm not ruling out a bad or improperly loaded low speed bearing in the new gearbox either. I hope I can get that info from Amarillo.
So why else would a 7 blade fane vibrate at 8 x running speed and not at 7 times at all?
I've got the Cooling Tower Institute VA spec and will see how these things measure up in displacement WRT motor and fan speed but I'm not really sure how to consider the 8 x when I look at their charts. It's not vane passing frequency. Except for their advice on how to find a bad ball bearing (number of balls times running speed), the spec is very helpful with charts based on the various types of construction. I would share it, but it is copyrighted material that can be found for sale on their site.