P Hine
This is some data from a Homogenizer Motor bearing. Motor is a Baldor 250 Hp. It is on a VFD. As you can see from the data there was a problem. Very audible also. My question, why does the data not show the outer race fault more clearly? I a at a loss to explain the 10K CPM that shows on these motors. We replaced the bearing and also installed a SGS grounding system on the ODE. These motors have VFD cable pulled to them and are still experiencing the fluting. This is the second time in 6 months we replaced the bearings on this motor. Hopefully the grounding will help. IMG_0688.JPG
Reply 0 0
OLi
Correct me but I believed the insocoat and similar was on the outside of the outer ring and fragile to scratches when mounting and composite was with 100% ceramic balls, but can be wrong. Ceramic balls are seriously hard. I had a customer lately complaining on hi noise level with ceramic balls, very small at 10 000RPM compared to steel any similar? With a very small rotor weight they may be bouncing around but they had some pretension to reduce looseness. Olov
Good Vibrations since early 1950's, first patented vibrometer 1956 in the US.
http://www.vtab.se
Reply 0 0
MarkL
That's the point I was trying to make Oli. 

I've only heard of ceramic balls being used mainly in motorsport applications on small size 6000 series bearings.
I'm a Vibration analyst, if you see me running away from a machine, try and keep up!
Reply 0 0
OLi
Ceramic are used in rotating gyros up to 20 000 RPM in aero with good results when overhauling. In normal use they are only a last resort due to the price. Olov
Good Vibrations since early 1950's, first patented vibrometer 1956 in the US.
http://www.vtab.se
Reply 0 0
Ron Brook

All right, let's try this again......
There is only one way to prevent EDM from EVER occurring again.  Throw away the expensive insocoat and ceramic bearings.  Throw away the AEGIS rings.  Throw away the non-conductive grease (yea, it doesn't conduct current, but it also doesn't lubricate). 
IF the motor is over a 440 frame size, and I believe the motor that started this thread is, then you must insolate the NDE bearing to break up the low frequency current path.  If you just do the simple, and correct things, all of those other bandages are not necessary.  You insulate the NDE bearing from the bearing housing.  Bore out the bracket and insert a non-conductive sleeve.  The sleeve will usually be approx. 3/8 of and inch in diameter thickness.  Also put a non-conductive disc on each side of the bearing to prevent grounding on the inner and outer bearing caps.  That's it.  No need to ever use a bearing more expensive than the standard bearing.  Once the NDE bearing has been successfully isolated, remember that bearing RTD's must also be insulated and if a tach is added to the motor shaft, it also must be isolated.
For all motors on VFD applications (See?  What I stated above is usually needed to prevent EDM even without a VFD in the picture!), run the appropriate power cable from the VFD to the motor.  This cable has a thin copper sheath that surrounds all three power leads.  It is run in one continuous cable.  Unwrap the copper inside the motor terminal box and ground it to a lug on one of the bolts that holds the motor terminal box to the motor frame.  On the inverter side, unwrap the copper sheath inside the VFD cabinet and ground it to the PE ground terminal, NOT the ground bus running at the bottom of the MCC cabinet.
I have used this method for EVERY EDM issue I ever encountered in the field while working for Reliance Electric/Rockwell/Baldor/Integrated Power Services and NEVER had a call back.
It's not complicated folks.  Basics

 

Reply 0 0
JuddJones
http://giphy.com/gifs/15BuyagtKucHm
Reply 0 0
OLi
Well, it is the hi freq. that is the problem and when you buy a expensive VFD enhanced motor that is the most obvious done one way or another, plating the motor shield with isolating oxide is a not so long lasting version as it erodes in less than 3 years. In some not so common cases it moves the trouble to the drive side and when that is isolated it moves the trouble to the fan bearing since the coupling was a shim pack, not so often but very irritating when it happens. Olov
Good Vibrations since early 1950's, first patented vibrometer 1956 in the US.
http://www.vtab.se
Reply 0 0
Ron Brook
P Hine,
The reason you don't see a clean BPFO or BPFI is because there are so many defects that the overall energy tends to be the excited bearing component resonances (that haystack between 60 Kcpm and 120 Kcpm) and it is modulated at the BPFO or BPFI.  That is the separation of the peaks that you get within the haystack.
As far as nice clean evenly spaced defects as opposed to variable and smeared defects, the difference is whether the motor is on a VFD that changes speed or across the line AC power.  It's the speed changes that cause the defects to smear.
Regards,
Ron Brook
Reply 0 0
Ron Brook
Big J,
I hope that was meant as a positive.  If so, I loved it!
Ron Brook
Reply 0 0
Ron Brook
OLI,
I had a customer try to tell me that my ideas were all BS.  I was flabbergasted!  What!  I tried to tell him that the coupling, being a conducting coupling, once the pretty enamel paint chipped off the coil spring, would carry the six amps on the motor shaft right through to the fan bearings.  It took 2 1/2 years for the paint to chip and the damage to occur.  See picture below.  This is the fan shaft where is sat inside the outboard fan bearing bore.......Pay me now or pay me later........ IMG_1421.jpg 
Reply 0 0
Ron Brook
OH, by the way,  found out the guy that didn't want to follow my advice had changed the corporate specifications to NOT include VFD duty cable because he didn't want to pay for it.
Reply 0 0
JuddJones
Quote:
Big J,
I hope that was meant as a positive.  If so, I loved it!
Ron Brook


This is the internet...Your perception is the reality! [biggrin]
Reply 0 0
MVS
Ron Brook: "If you just do the simple, and correct things, all of those other bandages are not necessary.  You insulate the NDE bearing from the bearing housing.  Bore out the bracket and insert a non-conductive sleeve.  The sleeve will usually be approx. 3/8 of and inch in diameter thickness.  Also put a non-conductive disc on each side of the bearing to prevent grounding on the inner and outer bearing caps.  That's it."

With all due respect Ron, I do agree with your post somewhat - however, you make it sound like an "easy inexpensive" fix, as per the above. It is never easy to convince a customer to have this type of "fix" done on their motor (down time being the biggest obstacle) and most certainly not cheap to do. I had one particular customer with this on-going issue and annual bearing replacement. Suggested insulating as you mentioned but to no avail and for legitimate reasons as to "down time"" and "turn around time" with the repair/refit. Finally was able to convince the maintenance mangers replacement to install a ceramic bearing since this could be done on-site and in-situ. It's been 8 years now in service with no issues whatsoever. 

At another site I convinced a customer to carry out a similar "fix"" as to what you mentioned and took it a step further by having the bearing journal "turned down" and built back up again with a spray on non-conductive epoxy material (I can't remember the name of the product). This was then machined back to the specifications prior to "turning it down". So far so good with that re-work also - to include a bearing change at one point and remounting of replacement bearing on to insulated journal without issue. 

So when you say "It's not complicated folks.  Basics". That's a bit of an "over statement" IMO - since the "fix" may not be complicated however, convincing and getting a customer to that point - can get very complicated not to mention frustrating. In closing - just to arbitrarily say "throw away the ceramic bearing fixes etc" - well, sometimes that is the "best fix" as relative to a lot of situations where this activity is present and on-going. Further to the "fix" you mention - yes it works without doubt - however, the sleeve and/or any machined and fitted inserts used, are just another area where issues can arise from a poor fit and/or on going wear whereas, the ceramic bearing can and usually does give long and reliable service life. 
"1xrpm is not always unbalance - but, unbalance is always 1xrpm"
Reply 0 0
arie mol

Over the recent years I have come across dozens of fluted bearing problems under VFD regime.
There is a simple fix: common mode filter (ferrite cores).
The basic problem is high frequency circulating current in the path {motor shaft / bearing nde / motor frame / bearing de / motor shaft} caused by a high frequency shaft voltage over the shaft ends induced by the VFD fast dU/dt switching. Insulated bearing does not help because the capacity (pF, nF) of the insulation layer acts as a conductive capacitor for high frequencies.

A common mode filter inserts L/R impedance between VFD output and motor terminals.

It does two things:

a) It effectively reduces the circulating current providing significant bearing life time extension.

b) It reduces the oscillating ring down frequency of the circulating current.

I fully gree with what Ron has posted. But I have two comments on his point of view:

1) Ferrite cores are a simpler fix.

2) Point b) : the lower frequency of the circulating current gives the bearing insulation a higher impedance in the circulating path. This also reduces circulating current through bearings. Summary: insulated bearing alone will not help very much, however togethet with common mode filter it may contribute to bearing life time extension. 

Modern VFD switches ultra fast, delta dc voltage within less than 1 µsec for P < 500 kW. This makes the application of common mode filter mandatory whereas this was not mandatory in the past when switching rise times were much slower.
End users in the industry in the Netherlands more and more become aware of this fundamental operational reliability problem. Still many OEM's deny all knowledge of this affair...


Reply 0 0
stace1g
Has anybody ever seen any fluting type damage on a non VFD driven induction motor? 

Gary
Reply 0 0
OLi
Yes in a ironmill where a old large VFD was found on the same transformer as several feed pumps and specially a exhaust fan, all did exhibit the same problems as a machine running on a VFD so my evaluation was that the VFD did send the trouble back to the grid segment that was on the same transformer as the VFD. Olov
Good Vibrations since early 1950's, first patented vibrometer 1956 in the US.
http://www.vtab.se
Reply 0 0